Study controls
Compare operating cases
Each preset starts from the default network.
Interactive study network
Source labels show solved MW injection. Negative means absorption. Breaker status and source controls are in the left panel.
Bus voltages & load schedules
| Bus | Voltage · pu ∠° | Voltage · kV L–L | Load · MW / Mvar |
|---|
Source dispatch
| Source | Model | MW injected | Mvar injected | Primary current · A |
|---|
Branch flow and losses
| Path | From-end MW / Mvar | To-end MW / Mvar | Loss MW / Mvar |
|---|
Branch powers are positive into the branch at each end. Their sum is branch loss. Conventional sources are fixed EMFs behind impedance; their MW/Mvar are solved, not dispatch setpoints.
BESS energy window
Positive BESS MW discharges; negative MW charges. Duration uses constant scheduled AC power, present SOC limits and the entered one-way efficiency. It excludes auxiliaries, temperature, degradation and voltage-dependent limits.
Fault-bus voltage phasors
A: cyan · B: amber · C: violet. RMS phasors, separate auto-scaled plots. Numerical values follow.
At the fault
| Phase | Fault current · A ∠° | Voltage · kV L–G ∠° |
|---|
Sequence quantities at the fault bus
| Sequence | Fault current · A ∠° | Voltage · pu ∠° | Driving-point Z · pu |
|---|
Source-terminal currents during fault
| Source | IA · A ∠° | IB · A ∠° | IC · A ∠° |
|---|
These are local terminal currents into the network. They include circulating currents and must not be added as scalar magnitudes. An off-nominal transformer changes current between its terminals.
Relay-location measurements
| Relay / CT location | Max phase · primary A | Max phase · secondary A | Residual · primary A |
|---|
Fault calculation trace
Solar and BESS use fixed positive-sequence current injections during the fault. Their magnitude and angle are explicit assumptions; no inverter controller, ride-through timing, negative-sequence controller or vendor-specific current-priority logic is simulated.
Time-current comparison
Cyan: feeder relay D. Amber: T1 relay U. Curves show element time; markers use the measured fault current at each location.
Timing for this fault
| Relay | Measured primary A | Element time · s | Breaker time · s | Total · s |
|---|
Magnitude-only phase-overcurrent comparison using max(|IA|, |IB|, |IC|). It excludes directionality, CT saturation, transient response, reset memory and logic. Utility B, DG and DER provide alternate infeeds: T1 relay U is not complete backup for every source. A time interval alone cannot establish full scheme selectivity.
Inverse-time equation
t = TMS × K / [(I / Ipickup)α − 1], for I > Ipickup. No operation is reported at or below pickup.
IEC standard inverse: K = 0.14, α = 0.02. Very inverse: K = 13.5, α = 1. Extremely inverse: K = 80, α = 2. The required interval is measured from feeder breaker clearing to upstream element operation.